SOLICITE UM ORÇAMENTO GRÁTIS AGORA!

Demonstração do formulário de contato (#3)

Interruptor de pressão de ar A402 HVAC para aquecedor de água - Peças de 0,5 psi

The A402 HVAC air pressure switch has a wide application in the water heater, wall-hanging stove, commercial air conditioning filtration system, VAV systems, and so on. Which are high quality and high precision.

HVAC Air Pressure Switch

Compartilhe esta página

HVAC Air Pressure Switch Description

The A402 HVAC air pressure switch belongs to our A4 series family which is high-quality and high precision. It uses the unibody construction design to replace the traditional microswitch construction type, which has better precision, longer life, and is more stable. The accuracy for the A4 HVAC air pressure switch series is ±3Pa, which is a high level on the market.

Meanwhile, it not only has a wide working pressure range that is from 40 to 500Pa, so it can meet many different devices’ requirements. As well as it has good performance in working temperature, which is from -40 to 110℃. So, the switch will not easy to be affected by the environmental temperature.

Besides, it also has a long operating life, it has 250000 cycles of electrical life and 1000000 cycles of mechanical life at least. What’s more, we not only have the air pressure switch but also have the air pressure sensors, which can detect different places’ valves at the same time.  For more REGAL pressure & flow switch sensor products, please click the link or contact us to get more details.

 

A402 HVAC Air Pressure Switch Size

A4 Air pressure switch size

A402 HVAC Air Pressure Switch Specification

Número do modelo A402 Air Pressure Sensing Switch
Meio de trabalho Ar ou gás de escape
Tipos de terminais Conector rápido padrão 187 (4,8*0,5 mm)
Interface do tubo 6,3 de diâmetro externo, adequado para tubos com diâmetro interno de 5 mm.
Circuito SPST NÃO
Avaliação 1A  24VDC & 0.5A 125/250VAC
Tensão de resistência 3000Pa (0,5Psi)
Vida útil elétrica 25000000 ciclos
saída de recuperação de gás Negativo
Temperatura de trabalho -40 a +110℃

 

Pressure Range Set Point
Set tolerance
Differential Range
ON=40 to 100 ±5 Pa(ON) & 8Pa(OFF) 15-30Pa
ON=100 to 200 ±8 Pa(ON) & 12Pa(OFF) 20-40Pa
ON=200 to 500 ±10 Pa(ON) & 15Pa(OFF) 10% – 20%