This page answers the questions engineers, appliance manufacturers and buyers ask most often about air pressure switches. The answers describe how the switch works, how to choose a set point and how to test a part in the field.
What is an air pressure switch?
An air pressure switch is a pressure-operated electrical switch that senses the pressure of air or flue gas and changes contact state at a preset set point. In gas appliances it usually proves that a fan is moving air before ignition is allowed.
How does an air pressure switch work?
A diaphragm or piston moves when the pressure difference across it changes. The movement operates a snap-action contact block, closing or opening the circuit. A spring sets the trip point, so the switch can be calibrated to a specific pressure.
Where are air pressure switches used?
Gas boilers and wall-hung boilers, gas water heaters, ovens and furnaces, HVAC air handling units, ventilation systems, air compressors and industrial pneumatic equipment.
What is the difference between an air pressure switch and an air pressure sensor?
A pressure switch gives an on/off contact at a set point and is used for control and safety interlocks. A pressure sensor gives a continuous electrical signal proportional to pressure and is used where the control system needs a measured value rather than a trip.
What are set point and differential?
The set point is the pressure at which the switch changes state. Differential is the gap between the cut-in and cut-out pressures. Together they define when a fan, pump or burner starts and stops.
What pressure range should I choose for a gas boiler?
Boiler air pressure switches typically operate in the tens to hundreds of pascals, depending on the fan and flue design. Select the range from the appliance manufacturer specification and confirm the trip point with a calibrated manometer.
How do I test an air pressure switch?
Apply a controlled pressure with a manometer or pressure tester, increase it slowly and record the point where the contact changes state; then reduce pressure and record the reset point. Compare both values with the datasheet and check contact continuity with a multimeter.
Why does my air pressure switch keep tripping?
Common causes are a blocked flue or intake, a failing fan, a blocked pressure sensing tube, condensate in the tube, or a set point that is too close to the normal operating pressure. Check airflow and tubing before replacing the switch.
Can the set point be adjusted on site?
Many Regal air pressure switches include an adjustment screw, but the safe adjustment range is limited and must be verified with a manometer. For safety-critical boiler interlocks, replace with the specified part rather than adjusting in the field.
What certifications should an air pressure switch have?
Look for an ISO 9001 quality system at the manufacturer and the product approvals required by your market, such as CE for Europe, CQC for China and RoHS/REACH material compliance. Regal supplies CE-marked pressure and flow products with material declarations on request.
Can Regal make a custom air pressure switch?
Yes. Regal customises set points, differentials, diaphragms, housings, connectors, mounting brackets and labelling for OEM programmes. Send the application, target pressure range and annual volume for a sample and quote.
How long does an air pressure switch last?
Mechanical air pressure switches from Regal are rated for up to 250,000 operating cycles under specified conditions. Actual life depends on pressure cycling, media, temperature and electrical load.
Still have a question? Send it to our engineers or read the pressure switch selection guide.